Transformer inrush current limiter Surpresses transformer inrush current

mainimage

When an idle transformer is re-energized, the transformer inrush current phenomenon occurs and causes various problems.

The Inrush Limiter T1 suppresses the inrush current by controlling the phase angle at which the circuit breaker closes. Since it's market launch, the Inrush Limiter has been praised for its effectiveness in limiting inrush currents. It has been used for numerous transformers in electrical power receiving substations for electrical utility companies, power receiving facilities in factories, and substations for wind-power generation facilities.

Overview and features

The inrush current phenomenon of a three-phase transformer is caused by mismatching polarities and absolute values of the initial magnetic flux induced by residual flux remnants in each phase core before the transformer is energized, and the system voltage immediately after the transformer is energized. This inrush current can be suppressed by limiting these mismatches. Technically, the key to suppressing the inrush phenomenon is inaccurately assessing the polarity and absolute value of residual fluxes in each phase core when the transformer is disconnected by the circuit breaker.

The value of residual flux that occurs when the transformer is disconnected is not the immediate magnetic flux that occurs when the circuit breaker is tripped. Residual flux is the final value of magnetic flux transients that occur immediately after disconnection. The Inrush Limiter integrates the transformer voltage (VT output voltage) by time to digitally calculate and capture the true residual flux. Specifically, it uses the transient waveform of the magnetic fluxes in the cores after the transformer is disconnected, and the value at which those fluxes converge. The next time the transformer is energized, phase angle control is applied to the timing of the circuit breaker to effectively suppress inrush current.

Product Video

Advantages

  • The Inrush Limiter can be used with any transformer and is not limited by capacity, voltages, connection style, impedance, or other transformer ratings. The type of circuit breaker and busbar design is also irrelevant.
  • The only required inputs are the three-phase VT voltage on the high voltage or low voltage side of the transformer, and the auxiliary switches of the circuit breaker. The only output is a time-delayed signal that operates at the optimum connection phase angle. The I/O interface is extremely simple and requires no tuning adjustment.
  • The core processing unit has a circuit board module with a digital processor that calculates, in real-time, the voltage waveform of each phase when the transformer is disconnected, and the magnetic flux waveform as the integral of the voltage input. This processor then calculates the optimum timing at which to connect the circuit breaker the next time the transformer is to be energized. This allows continued performance without maintenance or regular inspections.

Solutions

The inrush current phenomenon is a transient phenomenon that occurs when an idle transformer is re-energized. The transient effect appears as huge unbalanced sharp-edged waveforms across the three-phases that are several times larger than the rated current, and 20% voltage drops that can last from a half to several seconds. This can cause various failures to the load side nearby the transformer in substations that are used for many different applications. Kodensya's Inrush Limiter effectively suppresses the inrush phenomenon that occurs when operating the circuit breaker for transformers used in various applications.

Interconnected Substations for Distributed Power Generation Systems

Distributed power generation systems (wind power, solar power, small hydraulic power) are usually connected to low power transmission and distribution lines (over long distances at high impedance) where voltage drops associated with the inrush phenomenon are a serious concern. The Inrush Limiter plays an important role at these distribution substations.

Substation for Electrical Utility Companies

The Inrush Limiter effectively prevents voltage drops for all loads served by special high voltage systems and power distribution systems.

Large-scale Public Facilities & Power Receiving Stations for Factories

The Inrush Limiter prevents failures in power loads and their control systems where stable voltage and current is required.

Applications and Field Validation Results

  • This is for an electric utility company’s substation on a remote island. The low potential of the system raised concerns about voltage drops due to the inrush current of the power receiving transformer. The Inrush Limiter T1 was installed to prevent this. Figure 3-2 shows measured waveforms, recorded during field validation testing, of the inrush current and voltage drop with and without the Inrush Limiter.

    Transformer specificationsTr.1: 10MVA 22kV/6kV
    Tr.2: 6MVA 22kV/6kV

    After repeated opening and closing tests without the Inrush Limiter, the inrush phenomenon showed an inrush current of 411 A and a voltage drop of 14.8%. With the Inrush Limiter, the inrush current was suppressed to 91A and the voltage drop was held to within 1.9%.

  • A major chemical manufacturer owns an electrical furnace and its electrical power receiving substation. The substation consists of several banks of the power receiving transformers. When they energized a transformer in one of the banks, the other banks (connected to the primary side of the power system) showed a significant voltage drop. The Inrush Limiter T1 was installed to avoid this voltage drop and the disturbances it causes on manufacturing activities. Figure 3-4 shows measured waveforms, recorded during field validation testing, of the inrush current and voltage drop with and without the Inrush Limiter.

    Transformer specifications22MVA 44kV/11kV

    After repeated opening and closing tests without the Inrush Limiter, the inrush phenomenon showed an inrush current of 1,514A and a voltage drop of 7.1%. With the Inrush Limiter, the inrush current was suppressed to 83A and the voltage drop was held to within 0.2%. This manufacturer used a circuit breaker with a resistor for many years to suppress inrush currents in their 66-kV electrical power receiving substation. (The 66-kV serial resistor is used with an auxiliary circuit breaker to limit inrush current when the breaker is closed.) The Inrush Limiter has rendered these resistors obsolete, which are now removed.

  • Studies at an interconnected substation for a wind power generating system revealed voltage drops of 20% when the transformer was connected. It was necessary to suppress this to within 5%. The Inrush Limiter achieved less than 3%. (Each of the following countermeasures to achieve 5% or less were rendered obsolete:

    1. 1.Installation of a diesel generator
    2. 2.Specially designed transformer (change in leakage impedance, etc.)
    3. 3.Use of a serially-connected resistor and circuit breaker

    Figure 3-6 shows measured waveforms, recorded during field validation testing, of the inrush current and voltage drop with and without the Inrush Limiter.

    Transformer specifications30MVA 33kV/66kV

    After repeated opening and closing tests without the Inrush Limiter, the inrush phenomenon showed an inrush current of 839A and a voltage drop of 19.5%. With the Inrush Limiter, the inrush current was suppressed to 164A and the voltage drop was held to within 1.5%.

PRODUCT INFO

How Inrush Current Occurs and the Algorithm to Suppress It

When the transformer is disconnected from the system by manual operation, the three-phase cores remain magnetized, leaving residual flux φa,φb,φc in its original state. The next time the transformer is re-energized at phase timing θcl, the initial charge of the voltage on the side of the power supply system adds an initial magnetic flux φa(tcl),φb(tcl),φc(tcl) to the cores. If the residual flux φa,φb,φc and the initial magnetic flux φa(tcl),φb(tcl),φc(tcl) that occurs when the transformer is re-energized have the same polarity and a small scalar difference across each phase, the inrush phenomenon can be suppressed. But if the polarity differs on any of the phases and the scalar difference is large, the transient flux in the cores will overwhelm the saturation value and generate tremendous inrush phenomenon. Therefore, knowing what the correct scalar value is, including the polarity of the fluxes remnant in each core after the transformer is disconnected, is key to developing a control algorithm that can suppress inrush current. Incidentally, the polarity and magnitude of this residual flux φa,φb,φc is significantly different from the flux φa(top0),φb(top0),φc(top0) that remains in the cores when the transformer is disconnected at time top0. The reason for this is illustrated below.

Above figure shows a representative phase of the transformer Tr circuit about to be energized from an unloaded state (where circuit breaker Br2 is disconnected). The line from the low voltage side of the transformer coil has a loop circuit based on floating capacitors and surge absorbers. This means that a brief transient voltage, current, and magnetic flux will occur immediately after circuit breaker Br1 on the high voltage side is disconnected. The voltage va(t),vb(t),vc(t) and current ia(t),ib(t),ic(t) attenuate and eventually disappear as the transient phenomenon dies down top1. The magnetic flux φa(t),φb(t),φc(t) in the cores (which is the integral of the voltage) undergoes a transient change which allows the final value at top1 to converge to a constant value φa(top1),φb(top1),φc(top1). This convergence value is the true residual flux in the core. Notice that the circuit is balanced on all three-phases before and after the transformer is disconnected. If circuit breaker Br1 trips the transformer with an extremely small inrush current, all three phases will trip at the same time top0 (there is no time delay among phases as with zero-cross tripping). As such, the conditions to keep the three-phase balanced during the transient phenomenon are preserved. This means that the residual flux in the core is balanced across the three-phases.

Above figure shows the transient phenomenon that was recorded by the Inrush Limiter after the transformer was disconnected. This installation is for a power receiving transformer (220/110kVA, 250MVA, Y-Δ, 60Hz) in a substation of an electric power company. The upper diagram shows the transient waveforms of the voltage (measured secondary VT voltage) and magnetic flux (generated by calculating the integral of the voltage). The lower diagram is a visual representation of the voltage and magnetic flux waveforms through a rotating phaser. The voltage phaser attenuates as it rotates and eventually disintegrates by the time top1 the transient phenomenon dies out. The magnetic flux phaser also shrinks as it rotates, and converges into a residual flux of a certain value while remaining balanced across the three-phases at top1. In each phase, the polarity and absolute value of the residual flux has a completely different scalar value than the magnetic flux the moment top0 the circuit breaker is disconnected. The Inrush Limiter calculates and captures the residual fluxes in each phase in an almost balanced state. φa(θop1),φb(θop1),φc(θop1). When the transformer is re-energized, the phase at which the circuit breaker closes is controlled so that phase timing θcl is approximately the same as phase θop1 of the residual flux. (See our Patented Method for details on the algorithm.)

Algorithm for Suppressing Inrush Current (Patented Method)

Numerous field data from many different substations prove how effective the Inrush Limiter is at suppressing the inrush phenomenon. See Applications for typical applications. Although the basic theory of the Inrush Limiter’s control algorithm is field-proven, Kodensya did extensive tests with a simulated power transmission system (220 volts) to validate the control method, as reported below.

  • In the simulated power transmission test, the transformer was repeatedly disconnected at phase timing θop0. Each time, the voltage waveform (actual measurements) of each phase in the transient period was recorded and used, in turn, to calculate and record the magnetic flux waveform (generated by integration), and a rotating phaser of the size and phase angle θop1 of the three-phase residual flux at the end of the transient period. The peak inrush current (θop1,θcl,I) at phase angle θcl, at which the circuit breaker was closed to re-energize the transformer, was also recorded. Figure 2-3 shows a 3-D curved surface drawing of the results measured (θop1,θcl,I) from repeated opening and closing tests.

  • Figure 2-4 takes the same test results and shows the area covered by the maximum and minimum inrush current as coordinates (θop1,θcl). This figure shows with great precision that when θop1 and θcl are in just about the same phase, inrush current I is at an extreme low, and when θop1 and θcl are at 180-degree opposite phases, inrush current I is at its peak. Figure 2-5 shows the peak inrush current waveform that was recorded when the circuit breaker was closed at opposite phases. Figure 2-6 shows how virtually all inrush current is eliminated by closing the circuit breaker at the optimum phase angle (according to the algorithm of the Inrush Limiter).

Optimum Algorithm: Matching Scalar Value to the Phase with the Smallest Residual Flux

The Inrush Limiter, immediately after the transformer is disconnected, calculates and captures the true residual flux in its disintegrated state at the end of the transient phenomenon as an idle equilateral triangle at phase angle θop1. The circuit breaker is controlled to re-energize the transformer where phase angle θcl is as close as possible to θop1. Figure 2-7 explains this control algorithm. The small triangle in the figure indicates the phaser for the residual flux. The phase with the smallest scalar value (phase a in the figure) is chosen as the reference phase. The scalar value of the reference phase a in the initial magnetic flux (the large triangle in the figure) matches the scalar value of the residual flux (becomes ∆Φa=0) at two-phase angles every cycle (Figures 2-7 and 2-8). In figure 2-7, the polarities of the residual flux and initial magnetic flux of phase b match, and ∆Φb is sufficiently small. This is also true for phase c. In this way, Inrush Limiter’s algorithm finds and uses the optimum phase angle at which to close the circuit breaker. Figure 2-8 shows the other timing at which ∆Φa=0. In this case, an extremely large inrush current would occur because the polarities of the residual flux and initial magnetic flux for phases b and c are at almost exact opposite phases, and ∆Φb, ∆Φc are extremely large. The polarities of the fluxes for phases b and c in both Figures 2-7 and 2-8 are easy to recognize, and makes it possible to achieve the optimum phase angle that is shown in Figure 2-7.

Need some help
about this product?

Get in contact with our friendly support staff.
We will be happy to assist you in all matters of your purchasing requirements and are looking forward to your inquiry.
All fields are required.

Your name
Company
Email
Phone
Message

We will use your privacy information for marketing purposes.

I agree.

Related Products

catalog

Inrush-Limiter T1

The Inrush Limiter T1 suppresses the inrush current by controlling the phase angle at which the circuit breaker closes.

VIEW MORE DETAIL